Cable Cross-Section Sizing Calculator
Find the minimum cable cross-section in mm² for a given current and cable length.
Uses IEC ampacity tables and voltage drop limits (metric system).
Cable Sizing in the IEC/Metric World Outside North America, cable size is specified in mm² (square millimetres) rather than AWG. Standard sizes in IEC 60364 are: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm². A higher number means a larger, thicker conductor with more capacity.
Two Selection Criteria As with AWG selection, IEC cable sizing must satisfy two requirements simultaneously:
- Ampacity, the cable must carry the load current without overheating based on installation method and ambient temperature.
- Voltage drop, the voltage at the load must not fall more than 4% below the supply voltage (IEC guideline; some standards allow 3%).
The selected size must pass BOTH tests.
Ampacity by Installation Method How a cable is installed dramatically affects how quickly heat dissipates:
- In conduit/raceway: worst cooling: use base ampacity values.
- Clipped direct to surface: 20% more ampacity than conduit (better cooling).
- In free air (suspended): best cooling: approximately 30% more than conduit.
- Underground: approximately 10% less than conduit (soil thermal resistance). These factors are multiplied against the base ampacity for the selected cross-section.
Material Factor Copper conductors carry approximately 25% more current than aluminum conductors of the same cross-section. Or equivalently, aluminum requires a cross-section approximately 1.6× larger for the same ampacity. Copper is standard for fixed wiring; aluminum is used for large service cables and overhead lines.
Voltage Drop Formula ΔV = 2 × ρ × L × I / A Where: ρ = resistivity of copper = 1.72 × 10⁻⁸ Ω·m (aluminum = 2.82 × 10⁻⁸ Ω·m) L = one-way cable length in metres I = load current in amps A = conductor cross-sectional area in m² (so convert mm² by dividing by 1,000,000)
The factor of 2 accounts for the outgoing and return conductors. Voltage drop percentage = (ΔV / V_supply) × 100. IEC 60364-5-52 recommends keeping the drop below 4% for final circuits (3% for some applications).
Reading the Results The calculator finds the smallest standard cross-section that satisfies both ampacity and voltage drop. If voltage drop forces a larger size than ampacity requires, the table will show which criterion is binding. For very long runs, voltage drop can require a cable two or three sizes larger than ampacity alone demands.
Practical Tips Always use the NEXT size up from the calculated minimum — cable sizes are a fixed series. For three-phase systems, voltage drop is reduced by a factor of √3 compared to single-phase for the same power. In hot climates (ambient above 30°C), derate ampacity by approximately 3–5% per 5°C above 30°C. In cable trays with many cables touching, further derating applies — consult IEC 60364-5-52 correction tables.
How we build and check this calculator
This calculator runs entirely in your browser, so the numbers you enter stay on your device. The math behind it is written by hand and tested against worked examples and standard references before the page goes live.
SuperGlobalCalculator is independently built and maintained. See how we build and verify our calculators.