Ad Space — Top Banner

Wire Gauge Calculator

Calculate the recommended AWG wire gauge based on current, distance, and acceptable voltage drop.
Supports feet and meters.

Recommended Wire Gauge

Wire gauge selection determines whether a cable can safely carry a given electrical current over a given distance without overheating or wasting excessive power through voltage drop.

The AWG system (American Wire Gauge): AWG numbers run counterintuitively — a lower AWG number means a thicker wire. AWG 4 is much thicker than AWG 14. Each three-step decrease in AWG roughly doubles the wire’s cross-sectional area and halves its resistance.

Voltage drop formula:

V_drop = (2 × L × I × R) ÷ 1000

Variable definitions:

  • V_drop = voltage lost along the wire (volts)
  • L = one-way cable length (feet)
  • I = current load (amperes)
  • R = wire resistance (ohms per 1,000 feet, from AWG table)
  • × 2 = accounts for the round-trip (positive and return conductors)

AWG copper wire reference table:

AWG Ω/1000 ft Max Amps (in conduit)
14 2.525 15 A
12 1.588 20 A
10 0.999 30 A
8 0.628 40 A
6 0.395 55 A
4 0.249 70 A
2 0.156 95 A

Worked example: A 20 A circuit runs 75 feet (one way) using AWG 12 wire: V_drop = (2 × 75 × 20 × 1.588) ÷ 1000 = 4.76 V On a 120 V circuit: 4.76 ÷ 120 = 3.97% voltage drop

Industry standards:

  • ≤ 3% drop — recommended for branch circuits (NEC guideline)
  • ≤ 5% total — maximum acceptable for feeder + branch combined
  • Upgrade to AWG 10 in this example to bring drop under 3%

Aluminum wire note: Aluminum wire (common in older homes and service panels) has about 1.6× the resistance of copper. Always use the aluminum column of resistance tables when dealing with aluminum conductors.


Ad Space — Bottom Banner

Embed This Calculator

Copy the code below and paste it into your website or blog.
The calculator will work directly on your page.